R-410A PT Chart

At 40°F, R-410A's dew (saturated vapor) pressure is about 118 psig. This chart pairs saturation temperature with bubble and dew pressure from −40°F through 150°F. Enter a temperature or pressure to look up the matching value; interpolation stays within the one-degree rows. Follow the equipment manufacturer's charging instructions. Use the TierMenu chart below for another lookup.

Interactive R-410A pressure-temperature lookup

Enter a known temperature or pressure. The lookup interpolates between table rows and displays bubble and dew values separately.

R-410A saturation table

°F

R-410A pressure / temperature

At 40.0°F

Saturation pressure

Bubble pressure

118.8psig

Dew pressure

118.4psig

Bubble and dew columns are reported separately. Use the column appropriate to the refrigerant and measurement context.

Complete R-410A pressure-temperature table

All 191 committed rows are shown below. Gauge pressure is in psig. Use the bubble or dew column as appropriate to the measurement; values are not extrapolated outside the published range.

R-410A saturation pressure · −40°F to 150°F · psig
TemperatureBubble (psig)Dew (psig)
−40°F10.810.7
−39°F11.411.3
−38°F12.112.0
−37°F12.712.6
−36°F13.413.3
−35°F14.114.0
−34°F14.814.7
−33°F15.615.5
−32°F16.316.2
−31°F17.116.9
−30°F17.817.7
−29°F18.618.5
−28°F19.419.3
−27°F20.220.1
−26°F21.020.9
−25°F21.921.8
−24°F22.722.6
−23°F23.623.5
−22°F24.524.4
−21°F25.425.3
−20°F26.326.2
−19°F27.327.1
−18°F28.228.1
−17°F29.229.0
−16°F30.230.0
−15°F31.231.0
−14°F32.232.0
−13°F33.233.1
−12°F34.334.1
−11°F35.435.2
−10°F36.536.3
−9°F37.637.4
−8°F38.738.5
−7°F39.939.7
−6°F41.040.8
−5°F42.242.0
−4°F43.443.2
−3°F44.644.4
−2°F45.945.7
−1°F47.246.9
0°F48.448.2
1°F49.749.5
2°F51.150.8
3°F52.452.2
4°F53.853.5
5°F55.254.9
6°F56.656.3
7°F58.057.8
8°F59.559.2
9°F60.960.7
10°F62.462.2
11°F63.963.7
12°F65.565.2
13°F67.166.8
14°F68.668.4
15°F70.370.0
16°F71.971.6
17°F73.573.3
18°F75.274.9
19°F76.976.6
20°F78.778.4
21°F80.480.1
22°F82.281.9
23°F84.083.7
24°F85.885.5
25°F87.787.4
26°F89.689.2
27°F91.591.1
28°F93.493.1
29°F95.495.0
30°F97.497.0
31°F99.499.0
32°F101.4101.1
33°F103.5103.1
34°F105.6105.2
35°F107.7107.3
36°F109.9109.5
37°F112.1111.7
38°F114.3113.9
39°F116.5116.1
40°F118.8118.4
41°F121.1120.6
42°F123.4123.0
43°F125.8125.3
44°F128.2127.7
45°F130.6130.1
46°F133.0132.6
47°F135.5135.0
48°F138.0137.5
49°F140.6140.1
50°F143.1142.6
51°F145.8145.2
52°F148.4147.9
53°F151.1150.5
54°F153.8153.2
55°F156.5156.0
56°F159.3158.7
57°F162.1161.5
58°F164.9164.4
59°F167.8167.2
60°F170.7170.1
61°F173.7173.1
62°F176.6176.0
63°F179.6179.0
64°F182.7182.1
65°F185.8185.1
66°F188.9188.3
67°F192.0191.4
68°F195.2194.6
69°F198.5197.8
70°F201.7201.1
71°F205.0204.4
72°F208.4207.7
73°F211.8211.1
74°F215.2214.5
75°F218.6217.9
76°F222.1221.4
77°F225.7224.9
78°F229.2228.5
79°F232.9232.1
80°F236.5235.7
81°F240.2239.4
82°F243.9243.2
83°F247.7246.9
84°F251.5250.7
85°F255.4254.6
86°F259.3258.5
87°F263.2262.4
88°F267.2266.4
89°F271.3270.4
90°F275.3274.5
91°F279.5278.6
92°F283.6282.7
93°F287.8286.9
94°F292.1291.2
95°F296.4295.4
96°F300.7299.8
97°F305.1304.1
98°F309.5308.6
99°F314.0313.0
100°F318.5317.6
101°F323.1322.1
102°F327.7326.7
103°F332.4331.4
104°F337.1336.1
105°F341.9340.8
106°F346.7345.7
107°F351.6350.5
108°F356.5355.4
109°F361.4360.4
110°F366.5365.4
111°F371.5370.4
112°F376.6375.5
113°F381.8380.7
114°F387.0385.9
115°F392.3391.2
116°F397.6396.5
117°F403.0401.9
118°F408.4407.3
119°F413.9412.8
120°F419.5418.3
121°F425.1423.9
122°F430.7429.6
123°F436.4435.3
124°F442.2441.0
125°F448.0446.8
126°F453.9452.7
127°F459.9458.7
128°F465.9464.7
129°F471.9470.7
130°F478.0476.8
131°F484.2483.0
132°F490.5489.3
133°F496.8495.6
134°F503.1501.9
135°F509.5508.4
136°F516.0514.9
137°F522.6521.4
138°F529.2528.0
139°F535.9534.7
140°F542.6541.5
141°F549.4548.3
142°F556.3555.2
143°F563.3562.2
144°F570.3569.2
145°F577.4576.3
146°F584.5583.5
147°F591.8590.8
148°F599.1598.1
149°F606.4605.5
150°F613.9613.0

How to use this saturation chart

At a known temperature, find the corresponding saturation pressure. At a known pressure, find the corresponding bubble and dew saturation temperatures. The interactive lookup uses the committed one-degree data and linear interpolation between adjacent rows. It returns no result outside −40°F to 150°F.

Superheat uses the dew (saturated vapor) temperature at suction pressure. Subcooling uses the bubble (saturated liquid) temperature at liquid pressure. The matching calculators handle those differences, but only the equipment manufacturer can specify the target and required operating conditions.

For blend refrigerants, retain the bubble/dew distinction. R-454B is shown as liquid/bubble and vapor/dew from its source table; the source pressure is converted from psia to psig. R-454B and R-32 require A2L service procedures. The R-22 chart is for servicing existing systems only.

Source and assumptions

  • Data source: CoolProp 8.0.0 saturation data committed with the application.
  • Lookup range: −40°F to 150°F in one-degree rows. Intermediate values use linear interpolation; out-of-range values are not extrapolated.
  • This chart does not set a charging target. Follow equipment instructions and applicable refrigerant safety requirements.
Download one-page printable R-410A chart PDF

R-410A PT chart FAQs

What is an R-410A PT chart?

It pairs R-410A saturation temperature with pressure. This chart includes separate bubble and dew columns from −40°F through 150°F.

Which column should I use?

Use the column appropriate to the measurement and manufacturer procedure. Superheat uses dew temperature; subcooling uses bubble temperature.

Can I look up pressure between whole degrees?

Yes. The lookup linearly interpolates between the committed one-degree rows. Values outside −40°F to 150°F are not extrapolated.

Does the chart set a charging target?

No. Compare measurements with the equipment manufacturer's instructions and required operating conditions.

What data does this chart use?

The committed R-410A saturation rows were generated with CoolProp 8.0.0. The application reads the stored data and does not calculate refrigerant properties at runtime.