Free HVAC calculator

Ductulator: Duct Size Calculator

Size round galvanized duct from airflow and friction rate, then convert to an equivalent rectangular size. Core formula: Friction (in. w.c./100 ft) = 0.109136 × Q^1.9 ÷ D^5.02. Use the TierMenu calculator below to apply it to your inputs.

CFM
in. w.c./100 ft

Often 0.08-0.10 for residential

in

We solve the other side for the same friction as the standard round size

Result

Calculated diameter

10.27in

Next standard round

12in

Velocity at calculated size

695FPM

Velocity at standard size

509FPM

Rectangular equivalent to 12 in round

8.0 × 15.5in

Round up the second side (e.g. 16 in) when ordering.

Results are estimates for reference. Verify against manufacturer data and your local code.

What the result means

The calculated diameter is an estimated round-duct size for the airflow and friction rate you enter. Because duct comes in standard sizes, we also show the next size up and the velocity you will actually get in it.

Rectangular duct is sized so its friction matches the standard round size. Enter one side and the calculator solves the other. Round the second side up to the nearest whole inch when ordering.

How it's calculated

  • Friction (in. w.c./100 ft) = 0.109136 × Q^1.9 ÷ D^5.02
  • D = (0.109136 × Q^1.9 ÷ friction)^(1 ÷ 5.02)
  • Velocity (FPM) = Q ÷ (π × (D ÷ 12)² ÷ 4)
  • Equivalent round De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25

Q in CFM, D in inches. Round galvanized steel at standard air (0.075 lb/ft³).

Standard round sizes: 4, 5, 6, 7, 8, 9, 10, 12, 14, 16, 18, 20, 22, 24 in.

Worked example

A supply trunk carrying 400 CFM designed at 0.08 in. w.c. per 100 ft.

  1. D = (0.109136 × 400^1.9 ÷ 0.08)^(1 ÷ 5.02) = 10.27 in
  2. Next standard size = 12 in
  3. Velocity in 12 in round ≈ 509 FPM

Use 12 in round, or an 8 in tall rectangular duct about 16 in wide.

Reference table

The values below are computed from the same calculator functions used above. They let you compare common sizes and operating points without replacing the interactive calculation or its assumptions.

Round galvanized duct capacity by standard diameter
Diameter0.06 in. w.c./100 ft0.08 in. w.c./100 ft0.10 in. w.c./100 ft
4 in28 CFM · 326 FPM33 CFM · 379 FPM37 CFM · 426 FPM
5 in51 CFM · 376 FPM60 CFM · 438 FPM67 CFM · 492 FPM
6 in83 CFM · 423 FPM97 CFM · 492 FPM109 CFM · 553 FPM
7 in125 CFM · 467 FPM145 CFM · 543 FPM163 CFM · 611 FPM
8 in178 CFM · 509 FPM207 CFM · 592 FPM232 CFM · 666 FPM
9 in242 CFM · 549 FPM282 CFM · 638 FPM317 CFM · 718 FPM
10 in320 CFM · 587 FPM372 CFM · 683 FPM419 CFM · 768 FPM
12 in518 CFM · 660 FPM603 CFM · 768 FPM678 CFM · 863 FPM
14 in779 CFM · 729 FPM906 CFM · 848 FPM1019 CFM · 953 FPM
16 in1108 CFM · 794 FPM1290 CFM · 924 FPM1450 CFM · 1039 FPM
18 in1513 CFM · 856 FPM1760 CFM · 996 FPM1980 CFM · 1120 FPM
20 in1999 CFM · 916 FPM2325 CFM · 1066 FPM2615 CFM · 1199 FPM
22 in2571 CFM · 974 FPM2991 CFM · 1133 FPM3364 CFM · 1274 FPM
24 in3235 CFM · 1030 FPM3764 CFM · 1198 FPM4233 CFM · 1348 FPM

Friction rates and velocities are calculated using the duct sizing functions in this calculator.

Sources and assumptions

Q in CFM, D in inches. Round galvanized steel at standard air (0.075 lb/ft³). Standard round sizes: 4, 5, 6, 7, 8, 9, 10, 12, 14, 16, 18, 20, 22, 24 in. Calculator formulas are published with their units so a technician can check a result instead of treating it as a black box. Where a code table, manufacturer specification or field measurement is required, use the applicable local source.

Last reviewed . Spot an error? Email support@tiermenu.com.

FAQ

What friction rate should I use?

Many residential designs use 0.06 to 0.10 in. w.c. per 100 ft, but the right number comes from the available static pressure and total effective length, as in ACCA Manual D.

Does this work for flex duct?

No. Flex has much higher friction than galvanized, especially when compressed or sagging. Use the manufacturer's flex friction chart.

Why jump from 10 to 12 in?

Those are the standard sizes in this list. Round up so the duct is never smaller than required.

How close is the rectangular size?

It is an approximate equivalent based on friction, not velocity. The rectangular duct is modeled to carry the same air at the same friction as the round duct, but its velocity will differ slightly.

Can I use this for return ducts?

Yes. The math is the same. Many designers choose a lower friction rate for returns to keep them quiet.

Using a reference result in the field

A calculator is most useful when the inputs match the job being checked. Confirm whether a value is nominal or measured, and whether readings were taken at design or actual operating conditions. The unit label beside the result is part of the result; do not carry a number into another calculation without checking its units.

Reference rows are provided for comparison, not as universal design limits. They use the values and conditions stated with each table. Elevation, air temperature, equipment and installation details can change a field result. Where the page calls out a code check, equipment rating or manufacturer table, that check remains part of the job.

Use the interactive inputs for the exact conditions at hand, then review the displayed formula and assumptions. If a value looks unexpected, change one input at a time and compare it with a known point in the reference table. Keep the measured readings and job-specific notes with the work record so another technician can understand how the result was obtained.

TierMenu provides these free calculators without an email gate. The results stay in this browser unless you choose to copy a shareable URL or print the page. A shared URL includes the calculator inputs in its query string; do not put personal or sensitive information in calculator fields.