Wire Size Calculator (Wire Gauge by Amps and Distance)

Choose a conductor size that meets both the load ampacity and the maximum voltage-drop limit. Core formula: Required ampacity = load × 1.25 for a continuous load; otherwise load. Use the TierMenu calculator below to apply it to your inputs.

A
V
ft

Source to load; do not enter round-trip distance.

Auto uses 60°C at 100 A or less, and 75°C above 100 A. You can choose a fixed rating.

%

The conductor is checked against this limit.

Result

Final conductor size

8 AWG

Deciding rule: Voltage drop

Required ampacity

20.00A

Calculated load

20.00A

Ampacity size

12 AWG

Voltage-drop size

8 AWG

Terminal rating used

60°C

Automatically selected from calculated load current.

Ampacity at final size

40A

Voltage drop at final size

3.13V

Final voltage drop

2.60%

116.9 V at load

Calculated from the supplied ampacity and voltage-drop tables. Confirm installation conditions, adjustments, overcurrent protection, and applicable code requirements.

Base ampacity only. Ambient correction and adjustment for more than three current-carrying conductors are not applied. This tool does not apply NEC 310.12 dwelling service or feeder sizing. Verify the NEC edition adopted in your jurisdiction.

Results are estimates for reference. Verify against manufacturer data and your local code.

What the result means

The result checks two independent limits: ampacity for the load and voltage drop along the one-way run. It selects the larger conductor size so the wire meets both checks within the supplied tables.

The ampacity table assumes 30°C (86°F) ambient and no more than three current-carrying conductors. Installation temperature, bundling and dwelling service or feeder rules can change the applicable value; those adjustments are not calculated here.

How it's calculated

  • Required ampacity = load × 1.25 for a continuous load; otherwise load
  • Single-phase voltage drop = 2 × K × I × L ÷ CM
  • Three-phase voltage drop = 1.732 × K × I × L ÷ CM
  • Selected size = the larger of the ampacity size and voltage-drop size

K = 12.9 for copper and 21.2 for aluminum; L is one-way length in feet; CM is conductor area in circular mils.

Small-conductor limits: copper 14 AWG = 15 A, 12 AWG = 20 A, 10 AWG = 30 A; aluminum 12 AWG = 15 A, 10 AWG = 25 A.

Watts mode assumes unity power factor. Confirm actual equipment nameplate current when available.

Worked example

20 A on 120 V single-phase, 50 ft one way, copper, 60°C terminals, noncontinuous load, with a 3% maximum voltage drop.

  1. Required ampacity is 20 A; 12 AWG meets the supplied ampacity table and small-conductor limit.
  2. 12 AWG drops 3.94 V, or 3.29%; it exceeds the 3% voltage-drop limit.
  3. 10 AWG drops 2.49 V, or 2.07%; it meets the voltage-drop limit.

Select 10 AWG copper. Voltage drop, not ampacity, determines the final size.

Reference table

The values below are computed from the same calculator functions used above. They let you compare common sizes and operating points without replacing the interactive calculation or its assumptions.

NEC Table 310.16 ampacities at 30°C ambient and not more than three current-carrying conductors
Conductor sizeCopper 60°CCopper 75°CCopper 90°CAluminum 60°CAluminum 75°CAluminum 90°C
14 AWG152025———
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil355420475285340385
750 kcmil400475535320385435

Values are base ampacity in amperes. Small-conductor limits apply separately: copper 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A; aluminum 12 AWG 15 A and 10 AWG 25 A. Ambient correction, conductor-count adjustment and NEC 310.12 are not applied.

Sources and assumptions

K = 12.9 for copper and 21.2 for aluminum; L is one-way length in feet; CM is conductor area in circular mils. Small-conductor limits: copper 14 AWG = 15 A, 12 AWG = 20 A, 10 AWG = 30 A; aluminum 12 AWG = 15 A, 10 AWG = 25 A. Watts mode assumes unity power factor. Confirm actual equipment nameplate current when available. Calculator formulas are published with their units so a technician can check a result instead of treating it as a black box. Where a code table, manufacturer specification or field measurement is required, use the applicable local source. Copper voltage-drop tables use K = 12.9 ohm-cmil/ft at 75°C.

Last reviewed . Spot an error? Email support@tiermenu.com.

FAQ

Why can the ampacity size differ from the selected size?

The selected size is the larger of the ampacity size and the voltage-drop size. A long run can need a larger conductor even when the smaller one carries the load.

How is a continuous load handled?

The required ampacity is multiplied by 1.25 when the continuous-load checkbox is selected.

Does this include temperature and conductor-count corrections?

No. It uses the supplied base table for 30°C ambient and not more than three current-carrying conductors. Apply any required code adjustments separately.

Does it size dwelling services and feeders?

No. The tool does not apply the alternate dwelling service and feeder rules in NEC 310.12.

Which NEC edition does the table use?

The ampacity values are the supplied Table 310.16 data. Check the edition adopted by your jurisdiction and confirm all installation conditions.

Using a reference result in the field

A calculator is most useful when the inputs match the job being checked. Where a field asks for a length, confirm whether it is one-way or total; where it asks for current, confirm whether the load is continuous or intermittent. The unit label beside the result is part of the result; do not carry a number into another calculation without checking its units.

Reference rows are provided for comparison, not as universal design limits. They use the values and conditions stated with each table. A different conductor material, temperature, power factor or load type can change a field result. Where the page calls out a code check, equipment rating or manufacturer table, that check remains part of the job.

Use the interactive inputs for the exact conditions at hand, then review the displayed formula and assumptions. If a value looks unexpected, change one input at a time and compare it with a known point in the reference table. Keep the measured readings and job-specific notes with the work record so another technician can understand how the result was obtained.

TierMenu provides these free calculators without an email gate. The results stay in this browser unless you choose to copy a shareable URL or print the page. A shared URL includes the calculator inputs in its query string; do not put personal or sensitive information in calculator fields.